Incoprea hypothesis tests · volume II
Heat pump performance falls sharply above a threshold temperature lift, so the same unit can be efficient in a mild climate and marginal in a cold one, and the threshold is set by the compressor rather than by the refrigerant.
Coefficient of performance should fall sharply above a lift threshold; the fall-off should not be a smooth thermodynamic decline.
Falsified by: Smooth performance fall-off across lifts would remove the threshold.
Fixed source at 2 C, sink temperature raised in 0.5 K steps to 95 K of lift. Coefficient of performance is 0.5 times the Carnot value (fixed second-law efficiency). R410A saturation pressure is fitted through 0.798 MPa at 0 C and 2.417 MPa at 40 C (Clausius-Clapeyron), giving the pressure ratio a single-stage compressor must deliver. A compressor limit of pressure ratio 8 marks the design cut-out.
code/tests/heat-pump-lift-threshold.py from the recorded run.| COP at 20 K lift | 6.88 |
| COP at 40 K lift | 3.44 |
| COP at 60 K lift | 2.29 |
| Pressure ratio 8 reached at (K) | 88 |
| COP at the cut-out | 1.56 |
COP falls from 6.88 at 20 K of lift to 2.29 at 60 K — a smooth hyperbolic decline, with the local elasticity constant at about 0.050 per K. The pressure-ratio limit of 8 is reached only at 88 K of lift, where the COP is still 1.56; the unit cuts out there for mechanical protection, not because performance has collapsed. There is no thermodynamic threshold.